Function description

  • Staircase time switch, electro-mechcanical
  • 4 conductor with floor lighting connection
  • 3 conductor without floor lighting (no longer permitted for new systems)
  • Retriggerable
  • No closed-circuit current consumption
  • Toggle switch for permanent light ON
  • Reliable due to synchronous motor drive
  • Simplest possible time setting and direct delay time readout on absolute scale
  • Precision mechanics and therefore exact switching period
  • Very low sensitivity to interference

Technical data

Operating voltage 230 V AC
Frequency 50 Hz
Width 1 modules
Installation type DIN rail
Stand-by consumption ~0 W
Capacity loss max. 0.7 W
Glow lamp load 50 mA
Setting range time 1 – 7 min
Type of connection Screw terminals
3/4-way conductors Yes
Secondary switching After 30 s
Type of contact NO contact
Opening width > 3 mm
Switching output Not potential-free (230 V)
Incandescent/halogen lamp load 2300 W
Fluorescent lamp load (conventional) lead-lag circuit 2300 VA
Fluorescent lamp load (conventional) parallel-corrected 1300 VA 70 µF
Energy saving lamps 150 W
LED lamp < 2 W 30 W
LED lamp 2-8 W 300 W
LED lamp > 8 W 300 W
Fluorescent lamp load (electronic ballast) 600 W
Fluorescent lamp load (conventional) series-corrected 2300 VA
Switching capacity 6 AX at 230 V AC, cos φ = 0.3, 16 A at 230 V AC, cos φ = 1
Switch for permanent light ✔️
Switch-off pre-warning
Multi-voltage input
Zero-cross switching
Test approval VDE
Housing and insulation material High-temperature resistant, self-extinguishing thermoplastic
Ambient temperature -10°C … 50°C
Protection class II
Type of protection IP 20

Downloads

Tender text DOC ELPA-8_0080002-Tender Text (25,6 kB)
Operating instructions PDF ELPA-8_0080002-Operating Instructions (2,1 MB)
CE declaration of conformity PDF ELPA 8-EU Declaration of Conformity (417,6 kB)
Data sheet PDF ELPA 8 (636,5 kB)

Accessories